Manufacturer Warranty

Click Here To View Manufacturer Warranty

CLUTTER INTO PROFIT

clutterInto

Turn your used or unwanted transformers or circuit breakers into cash or credit

Equipment Purchase Program

faq

SG3A0112PB

SKU:SG3A0112PB

By : Hammond Power Solutions

safeCheckout

Description

The Hammond Power Solutions (HPS) SG3A0112PB dry type transformer is a general-purpose distribution transformer designed for industrial and commercial applications. With a 112.5 kVA power rating, this transformer efficiently supplies appliances, lighting, heating systems, motorized machines, and other electrical loads. It operates at 60 Hz frequency with a 600 VAC primary voltage and a 120 VAC secondary voltage, ensuring reliable performance and energy efficiency.

Built with aluminum windings, the Hammond SG3A0112PB 600 volts transformer offers enhanced conductivity and durability. Its NEMA 3R-rated enclosure provides protection against rain, sleet, and snow, making it suitable for both indoor and outdoor installations. The transformer features a 150°C temperature rise and 220°C insulation class, ensuring consistent and long-lasting operation under demanding conditions.

Key Features of HPS SG3A0112PB 112.5 kVA Transformer:

• Compliant with DOE 10 CFR Part 431 energy efficiency standards.

• 150°C temperature rise, 220°C insulation class.

• Enclosure NEMA 3R – suitable for indoor and outdoor installations.

• Floor mounting with lug/pad connections.

• 10 kV Basic Insulation Level (BIL) for enhanced electrical protection.

• Meets ST-20 standard sound levels.

• Cold-rolled silicon steel laminations minimize core losses and improve efficiency.

• Precision-cut cores reduce burrs, enhancing performance and longevity.

• Moisture-resistant core coating prevents corrosion and extends durability.

• Robust core and coil interface enhances short-circuit resistance.

• Front-accessible high and low-voltage terminals for simplified installation.

Hammond Power Solutions

Additional information

  • DIMENSIONS

    27 × 28.3 × 36 in

  • KVA:

    112.5

  • PHASE:

    THREE

  • PRIMARY VOLTAGE:

    600

  • SECONDARY VOLTAGE:

    120

    208Y

  • WINDING MATERIAL:

    ALUMINUM

  • HZ:

    60

  • TEMP RISE:

    150

  • ENCLOSURE:

    NEMA 3R

  • TYPE:

    ENERGY EFFICIENT GENERAL PURPOSE DISTRIBUTION

  • OTHER:

    SCD19

  • TAPS:

    2+4-2.5%

  • TRADE NAME:

    HPS SENTINEL G

  • Weight

    680 lsb