A 112.5 kVA dry-type transformer is one of the most widely installed mid-range distribution units in North American electrical infrastructure used across commercial construction, industrial facilities, data centers, healthcare, and transportation projects throughout the U.S. All units in this category are three-phase, air-cooled, and available in a wide range of primary and secondary voltage configurations, enclosure types, and efficiency classes.
Bruce Electric Equipment has been supplying dry-type transformers across the U.S. since 1973. We stock new 112.5 kVA transformer units from leading manufacturers including Acme Electric and Hammond Power Solutions, covering the full range of standard voltage configurations, enclosure types, and efficiency classes. Used and reconditioned 112.5 kVA transformers are not listed online but are available upon request contact us for custom sourcing and RFQ support.
Weight 400–1,200 lbs depending on copper or aluminum windings. Most popular: 480V to 208Y/120V. K-Factor rated K-1 through K-20, harmonic mitigating, low-noise (-3 dB), and autotransformer configurations. 50/60 Hz dual-rated models available.
✔ 438+ units in inventory ✔ NEMA 1, 2, 3R, and 3R Heavy Duty enclosures ✔ Reconditioned units backed by warranty
The table below covers the full specification range across the 112.5 kVA dry-type transformer inventory we carry and source.
| Parameter | Specification |
|---|---|
| Power Rating | 112.5 kVA |
| Transformer Type | Dry-Type (air-cooled, no liquid insulation) |
| Phase | Three-Phase (3Ø) all inventory units are 3-phase |
| Frequency | 60 Hz standard; 50 Hz and 50/60 Hz on select models |
| Primary Voltage | 208V, 220V, 240V, 380V, 400V, 415V, 440V, 460V, 480V, 575V, 600V, 2400V, 4160V |
| Secondary Voltage | 208Y/120V, 480Y/277V, 240V, 240/120V, 220Y/127V, 480V, 400Y/231V, 380Y/219V, 240D, 600V and others |
| Temperature Rise | 80°C, 115°C, 130°C, or 150°C above 40°C ambient |
| Insulation Class | Class H (220°C) |
| Winding Material | Aluminium (Al) or Copper (Cu) – both available across inventory |
| Enclosure Types | NEMA 1, NEMA 2, NEMA 3R, NEMA 3R Heavy Duty, Indoor |
| Transformer Types | General Purpose Ventilated, K-Factor (K-1, K-4, K-13, K-20), Harmonic Mitigating, Low Noise (–3 dB), Ultra Energy Efficient, Drive Isolation, Autotransformer, Encapsulated |
| Compliance | DOE 2016, UL Listed, NEC Article 450 |
| Manufacturers | General Electric, Hammond Power Solutions, Rex Power Magnetics, Acme Electric, Jefferson Electric, EGS/SolaHD, Federal Pacific, MGM |
| Condition Available | New (listed online); Used & Reconditioned available upon request via RFQ |
| Ships To | All 50 U.S. states |
Bruce Electric also supports specialty and custom transformer configurations depending on manufacturer availability and application requirements.
Weight varies by phase, winding material, and enclosure. Use the table below for freight planning and structural load assessment. For certified dimensions and exact shipping weight, request the manufacturer datasheet with your quote.
| Configuration | Approx. Weight | Notes |
|---|---|---|
| 3-Phase, Aluminum Wound, NEMA 1/2 | ~600–900 lbs | Most common configuration in inventory |
| 3-Phase, Copper Wound, NEMA 1/2 | ~800–1,100 lbs | Higher conductivity; preferred for long service life |
| NEMA 3R / NEMA 3R Heavy Duty Adder | +75–150 lbs | Added for outdoor weatherproof enclosure types |
| Encapsulated Units | Varies by model | Request certified weight per unit from datasheet |
Output amps depend on secondary voltage and phase configuration.
Formulas:
Three-phase: Amps = 112,500 ÷ (Volts × 1.732)
Single-phase: Amps = 112,500 ÷ Volts.
The tables below cover primary amps and secondary amps for the voltage levels present in our 112.5 kVA transformer inventory. Use these values for overcurrent device sizing per NEC Article 450, feeder conductor ampacity selection, and panel schedule design. Always verify against the unit nameplate before finalizing protection settings.
| Primary Voltage | Phase | Formula | Primary Amps |
|---|---|---|---|
| 480V | 3Ø | 112,500 ÷ (480 × 1.732) | ~135 A |
| 208V | 3Ø | 112,500 ÷ (208 × 1.732) | ~312 A |
| 600V | 3Ø | 112,500 ÷ (600 × 1.732) | ~108 A |
| 240V | 3Ø | 112,500 ÷ (240 × 1.732) | ~271 A |
| 440V | 3Ø | 112,500 ÷ (440 × 1.732) | ~148 A |
| 415V | 3Ø | 112,500 ÷ (415 × 1.732) | ~157 A |
| 380V | 3Ø | 112,500 ÷ (380 × 1.732) | ~171 A |
| 2400V | 3Ø | 112,500 ÷ (2400 × 1.732) | ~27 A |
| 4160V | 3Ø | 112,500 ÷ (4160 × 1.732) | ~16 A |
| Secondary Voltage | Phase | Formula | Secondary Amps |
|---|---|---|---|
| 208Y/120V | 3Ø | 112,500 ÷ (208 × 1.732) | ~312 A |
| 480Y/277V | 3Ø | 112,500 ÷ (480 × 1.732) | ~135 A |
| 240V | 3Ø | 112,500 ÷ (240 × 1.732) | ~271 A |
| 240/120V | 3Ø | 112,500 ÷ (240 × 1.732) | ~271 A |
| 220Y/127V | 3Ø | 112,500 ÷ (220 × 1.732) | ~295 A |
| 480V | 3Ø | 112,500 ÷ (480 × 1.732) | ~135 A |
| 400Y/231V | 3Ø | 112,500 ÷ (400 × 1.732) | ~162 A |
| 380Y/219V | 3Ø | 112,500 ÷ (380 × 1.732) | ~171 A |
| 240D / 240D/120CT | 3Ø | 112,500 ÷ (240 × 1.732) | ~271 A |
| 600V | 3Ø | 112,500 ÷ (600 × 1.732) | ~108 A |
A 112.5 kVA step-down transformer reduces voltage from primary to secondary most commonly 480V to 208Y/120V for North American commercial power distribution. A 112.5 kVA step-up transformer increases voltage, for example from 208V to 480Y/277V, to feed higher-voltage equipment from a lower-voltage source. In most dry-type designs, the same physical unit can serve either function depending on wiring but always specify intended primary and secondary voltage to ensure correct nameplate design, warranty coverage, and NEC compliance.
| Primary (Source) | Secondary (Load) | Phase | Typical Application |
|---|---|---|---|
| 480V | 208Y/120V ( Most Popular ) | 3Ø | Commercial panels, office buildings, retail |
| 480V | 480Y/277V | 3Ø | Lighting distribution, isolation applications |
| 480V | 240D | 3Ø | Industrial motor loads, legacy delta systems |
| 480V | 250D/120CT | 3Ø | Resistance welding, specialized process equipment |
| 600V | 480Y/277V | 3Ø | Canadian service entry, cross-border industrial |
| 600V | 208Y/120V | 3Ø | Direct 600V to utilization voltage |
| 480V | 240/120V | 1Ø | Residential-style service in commercial buildings |
| 240V | 120/115/110V | 1Ø | Control circuit voltage reduction |
| Primary (Source) | Secondary (Load) | Phase | Typical Application |
|---|---|---|---|
| 208V | 480Y/277V | 3Ø | Powering 480V equipment from 208V service |
| 240V | 480Y/277V | 3Ø | VFD feeds, motor starters needing higher voltage |
| 380V | 480V | 3Ø | International equipment on U.S. service |
| 208V | 480V | 1Ø | Single-phase step-up for specific equipment feeds |
1. Three-phase configurations across all standard and specialty types
2. Air-cooled dry-type construction no oil, no liquid maintenance, no spill risk
3. Copper or aluminium windings to balance performance requirements and project budget
4. NEMA 1, NEMA 2, and NEMA 3R enclosures for indoor and outdoor installation
5. DOE 2016 compliant on all new units; Super-Efficient models available (Acme TPC3-series, Hammond HPS Super centurion)
6. Specialty types: K-Factor rated, Harmonic Mitigating, Low Noise (–3 dB), and Autotransformer configurations in inventory
7. 50 Hz / 60 Hz dual-rated models available for international equipment compatibility
1. Commercial buildings and office facilities – 480V to 208Y/120V step-down for tenant panels and lighting
2. Manufacturing and industrial plants – motor control centers, CNC equipment, and process line distribution
3. Healthcare and medical facilities – isolated power systems for ORs and critical care areas, often paired with UPS systems
4. Data centers and IT infrastructure – 480V to 208V step-down feeding server PDUs and UPS bypass panels
5. Transportation and infrastructure – transit stations, airports, and rail facility power distribution
6. Construction sites – temporary 480V-to-208Y/120V distribution for site panels and temporary power
Bruce Electric is a trusted supplier of 112.5 kVA dry-type transformers, offering a wide selection of new units to meet diverse project specifications. With over 50 years of industry experience, we provide fast access to in-stock transformers in multiple voltage configurations, phases, and NEMA enclosure types. Customers benefit from expert technical support for accurate sizing and configuration, and equipment that meets UL, DOE, and NEC standards. Used and reconditioned 112.5 kVA transformers are available upon request through our sourcing and RFQ process contact us for current availability. Backed by nationwide shipping and warranty coverage, Bruce Electric delivers reliable, cost-effective transformer solutions with quick turnaround times.
For a three-phase secondary at 208Y/120V: Amps = 112,500 ÷ (208 × 1.732) = approximately 312 A. For single-phase at 240V: 112,500 ÷ 240 = approximately 469 A. Always confirm against the nameplate for final NEC 450.3 overcurrent device sizing.
At a 480V three-phase primary: Amps = 112,500 ÷ (480 × 1.732) = approximately 135 A. This figure is used for feeder conductor sizing and upstream overcurrent protection selection per NEC Article 450.
Weight typically ranges from 400 to 1,200 lbs depending on phase (single vs. three-phase), winding material (copper vs. aluminum), and enclosure type. Three-phase copper-wound units in NEMA 1 enclosures are at the upper end. Always request certified shipping weight for structural loading and freight planning.
New unit pricing varies by manufacturer, voltage configuration, winding material, and efficiency class. Contact Bruce Electric for a current quote. Used and reconditioned 112.5 kVA transformers are available upon request through our RFQ process and can offer 20–50% savings versus new.
Yes. All new low-voltage dry-type distribution transformers sold in the U.S. must meet DOE 2016 minimum efficiency standards. Super-Efficient series units (Acme TPC3-series, Hammond HPS Super-centurion) exceed these minimums and deliver additional lifecycle energy savings.