A 15 kVA dry type transformer is one of the most widely specified sizes in commercial and light industrial electrical work, used for stepping down 480V building service to 208Y/120V for panel distribution, feeding lighting and HVAC control circuits, powering machine tool feeders, and supporting branch distribution in tenant fit-outs, institutional facilities, and construction projects where a compact, reliable voltage conversion solution is required.
At Bruce Electric Equipment Corp., we supply new, used and reconditioned 15 kVA transformers in single phase and three phase configurations. Since 1973, Bruce Electric has specialized in dry type transformers and electrical distribution equipment from leading manufacturers including Acme Electric, Hammond Power Solutions (HPS), Eaton and more. Our team can help source the right unit for your application. We offer fast nationwide shipping across the United States along with technical support.
| Parameter | Available Options |
|---|---|
| Phase | Single-Phase, Three-Phase |
| Frequency | 60 Hz (standard); 50/60 Hz (export models); 50 Hz |
| Primary Voltage | 120V – 4160V (model-dependent) |
| Winding Material | Aluminium or Copper |
| Temperature Rise | 80°C, 115°C, 130°C, 135°C, 150°C, 180°C |
| Enclosure | NEMA 1, NEMA 2, NEMA 3R, NEMA 3R Encapsulated, NEMA 3R Heavy Duty, NEMA 3R Stainless Steel, Encapsulated |
| Insulation Class | Class H (220°C) standard for 150°C rise units |
| Taps | Varies by model; 2–6 taps at 2.5% FCAN/FCBN typical |
Bruce Electric’s 15 kVA inventory covers a broader range of voltage configurations than most distributors carry across all kVA ratings combined. The following are confirmed from actual inventory.
| Primary Voltage | Secondary Voltage | Application |
|---|---|---|
| 480V | 208Y/120V | 192 SKUs – North American commercial step-down; feeds 208V/120V tenant and floor panels |
| 208V | 208Y/120V | Step-down where 208V is the building service; maintains 208Y/120V distribution |
| 600V | 208Y/120V | Canadian commercial and industrial facilities; most common Canadian config |
| 480V | 480Y/277V | Establishes neutral on delta 480V source; 277V for commercial lighting ballasts and LED drivers |
| 208V | 480Y/277V | Step-up from 208V service to feed 480V equipment |
| 240V | 208Y/120V | Step-down from lower-voltage service; commercial and light industrial |
| 600V | 480Y/277V | Canadian facilities requiring 277V lighting distribution |
| 480V | 240V | Delta secondary applications; ungrounded 240V three-phase loads |
| 480V | 240/120V | Delta-secondary with center-tap for 120V single-phase loads |
| 480V delta | 208Y/120V | Delta primary to wye secondary; industrial delta-source facilities |
| 240V | 480Y/277V | Step-up from 240V service to 480Y/277V for mixed lighting/equipment feeds |
| 480V | 400Y/231V | International equipment requiring IEC-standard voltage |
| 380V | 208Y/120V | European/international primary to North American secondary |
| 415V | 208Y/120V | UK and international primary to North American secondary |
| 440V | 220Y/127V | Export and international three-phase applications |
| 460V | 230Y/133V | International step-down, export OEM equipment |
| 208V | 480V | Step-up for 480V equipment from 208V service |
| 208V | 400Y/231V | International secondary from North American primary |
| 2400V | 208Y/120V, 480Y/277V, 600Y | Medium voltage distribution to LV utilization |
| 4160V | 208Y/120V, 480Y/277V, 600Y | MV utility step-down at point of load |
| Primary Voltage | Secondary Voltage | Application |
|---|---|---|
| 240 × 480V | 120/240V | Dual-primary step-down; most common single-phase config (25 SKUs) |
| 600V | 120/240V | Canadian single-phase service to 120/240V |
| 208V | 120/240V | Single-phase step-down from 208V panel |
| 480V | 120/240V | Single-phase step-down from 480V service |
| 277V | 120/240V | Step-down from 277V lighting circuit to 120V |
| 120/208/240/277V | 120/240V | Multi-tap primary; maximum installation flexibility |
| 190/200/208/220V | 120/240V | International multi-tap, export applications |
| 2400V | 120/240V | Medium voltage single-phase to 120/240V |
| 4160V | 120/240V | MV single-phase step-down |
Full-load amperage is determined by the secondary voltage and phase configuration. Use these formulas:
Single-phase: FLA = 15,000 ÷ Secondary Voltage
Three-phase: FLA = 15,000 ÷ (Secondary Voltage × 1.732)
| Configuration | Secondary Voltage | Full Load Amps (FLA) |
|---|---|---|
| Single Phase | 120V | 125.0 A |
| Single Phase | 240V | 62.5 A |
| Single Phase | 277V | 54.2 A |
| Three Phase | 208Y/120V | 41.6 A |
| Three Phase | 240V | 36.1 A |
| Three Phase | 480V | 18.0 A |
| Three Phase | 480Y/277V | 18.0 A |
A 15 kVA transformer provides adequate load capacity for small sub-panels, lighting circuits, HVAC controls, machine tool feeders, and commercial branch distribution. For larger load requirements, see our 30 kVA, 25 kVA, or 45 kVA transformer categories.
A 15 kVA step up transformer raises a lower incoming voltage to a higher output voltage. The most common application is feeding 480V-rated equipment from a 208V or 240V service, a frequent requirement when installing imported machinery, upgrading control panels, or reverse-feeding distribution in facility renovations. All step-up units in our inventory are three phase dry type, available from GE, Acme Electric, Federal Pacific, EGS/SolaHD, Jefferson Electric, and Hammond Power Solutions.
15 kVA Step-Up Configurations Available:
| Primary Voltage | Secondary Voltage | Phase | Example Unit |
|---|---|---|---|
| 208V | 480V | Three Phase | GE 9T83B3031 |
| 208V | 480Y/277V | Three Phase | Acme Electric T3793671S |
| 208V | 480Y/277V | Three Phase | Federal Pacific T204H15E |
| 208V | 480Y/277V | Three Phase | EGS/SolaHD ET84H15 |
| 208V | 277V / 480Y | Three Phase | Hammond Power Solutions |
| 240V | 480Y/277V | Three Phase | Acme Electric T3796931S |
| 240V | 480Y/277V | Three Phase | EGS/SolaHD ET85H15S |
| 240V | 277V / 480Y | Three Phase | Hammond Power Solutions |
A 15 kVA step down transformer reduces a higher primary voltage to a lower, usable secondary voltage. This is the most common transformer type in commercial and industrial electrical work, stepping 480V three-phase building distribution down to 208Y/120V for panels, outlets, and equipment, or 480V single phase down to 120/240V for lighting and branch circuits. We also carry 600V primary configurations for Canadian facilities and industrial plants running 600V distribution.
15 kVA Step-Down Configurations Available:
| Primary Voltage | Secondary Voltage | Phase | Example Unit |
|---|---|---|---|
| 480V | 208Y/120V | Three Phase | GE 9T10C1001 |
| 480V | 208Y/120V | Three Phase | Acme Electric TPC3533113S |
| 480V | 208Y/120V | Three Phase | EGS/SolaHD 3H13T2H15S |
| 480V | 240D/120CT | Three Phase | Jefferson Electric 423-9167-000 |
| 480V | 240Y/139V | Three Phase | GE (multiple) |
| 480V | 380Y/219V | Three Phase | GE (multiple) |
| 480V | 416Y/240V | Three Phase | MGM |
| 480V | 120/240V | Single Phase | Federal Pacific S2T15E |
| 480V | 240/120V | Single Phase | Acme Electric PT061150015LS |
| 277/480V | 208/277V | Single Phase | Acme Electric GP1215000S |
| 240 × 480V | 120/240V | Single Phase | Acme Electric T2535173S |
| 277V | 120/240V | Single Phase | Acme Electric T2536771S |
| 600V | 208Y/120V | Three Phase | Acme Electric T3793331S |
| 600V | 208Y/120V | Three Phase | Hammond Power Solutions P015PBKF |
| 600V | 240/120V | Three Phase | GE 9T83B3614 |
| 600V | 416Y/240V | Three Phase | MGM |
| 600V | 380Y/219V | Three Phase | MGM |
| 600V | 120/240V | Single Phase | Acme Electric T2536171S |
All 15 kVA transformers we stock are dry type units that use air cooling instead of oil, making them ideal for indoor commercial, healthcare, educational, and data center applications. Available options include general purpose, encapsulated, K-factor rated (K4, K13, K20), buck-boost, and isolation transformers for applications ranging from harmonic mitigation and voltage correction to noise reduction and electrical isolation. Contact our team for assistance with specific enclosure, temperature rise, or configuration requirements.
Enclosure Selection: NEMA 1 or NEMA 2 for clean, dry indoor locations. NEMA 3R for outdoor or damp environments. NEMA 3R Stainless Steel for wash-down, food processing, or coastal chemical exposure. For more information, read the blog: NEMA Enclosure Ratings Explained: Guide to NEMA Types, Chart & Applications.
1. Commercial office and retail buildings: Commercial office and retail buildings commonly use 15 kVA transformers for branch panels, lighting circuits, and tenant power distribution.
2. Lighting distribution. 15 kVA units can support commercial lighting loads, control circuits, and voltage conversion for facility lighting systems.
3. Light manufacturing and assembly. These transformers are used for machine tool feeders, small production equipment, control panels, and localized power distribution.
4. Data centers and server rooms: Data centers and server rooms use dry type transformers for reliable power distribution in IT, UPS, and support infrastructure.
5. Healthcare and institutional facilities: Healthcare and institutional facilities use 15 kVA transformers for dependable electrical distribution in critical and facility-support applications.
6. International and export OEM. Multi-voltage and export configurations help match North American equipment to international electrical systems.
7. Outdoor and industrial installations. NEMA 3R and encapsulated units are suitable where damp-location or outdoor protection is required.
8. Renovation and replacement. 15 kVA transformers are commonly used for replacing failed units, upgrading panels, and supporting tenant improvement projects.
Before installation, verify the transformer nameplate, voltage, phase, enclosure rating, load requirements, and applicable NEC requirements. Installation should be completed by a qualified electrical professional.
1. Ventilation. Maintain manufacturer-required airflow clearance to prevent heat buildup.
2. Overcurrent protection. Size primary and secondary protection based on NEC Article 450, nameplate data, voltage, and conductor sizing.
3. Conductor sizing. Select conductors based on full-load amps, insulation rating, terminal temperature limits, and installation conditions.
4. Grounding and bonding. Confirm grounding requirements, especially for separately derived secondary systems.
5. Enclosure rating. Use NEMA 1 or NEMA 2 for suitable indoor locations; use NEMA 3R or encapsulated options where outdoor or damp-location protection is required.
6. Taps. Verify available tap settings before energizing the transformer.
7. Mounting and access. Allow space for wiring, inspection, ventilation, maintenance, and future replacement.
8. Weight and handling. Confirm dimensions, shipping weight, and lifting requirements before delivery.
Bruce Electric Equipment Corp. has been a trusted source for dry type transformers and electrical distribution equipment since 1973. Contractors, facility managers, MRO buyers, and OEMs across the United States rely on us because we carry the inventory depth, product knowledge, and service infrastructure that generic electrical distributors don’t. When you need the right 15 kVA transformer correct voltage, phase, enclosure, and winding without chasing multiple suppliers, Bruce Electric is where professionals come first.
1. New, surplus & reconditioned. Every refurbished unit is inspected, tested, and covered by our BEE warranty (up to 2 years).
2. Fast shipping. Most units ship same-day or next-day, nationwide.
3. Spec support. Our team matches voltages, enclosures, and replacement units on request.
4. Hard-to-find units. Not listed online? Contact us. We source non-catalogue and discontinued configurations regularly.
A 15 kVA transformer has a 15,000 VA apparent power rating. Real usable kW depends on power factor. At 0.9 power factor, 15 kVA equals approximately 13.5 kW.
A 15 kVA transformer at 480V single-phase supplies approximately 31.25 amps. At 480V three-phase, it supplies approximately 18.04 amps.
Yes, if the transformer has a suitable outdoor-rated enclosure, such as NEMA 3R or another appropriate enclosure rating for the installation environment. Always confirm the enclosure rating before outdoor installation.
1. Dry Type Transformer Testing & Troubleshooting Guide